.DLR334 SeriesTWO RELAYS ANDSETPOINTS OPTIONOPERATION/INSTALLATIONMANUAL PN 74844
APPENDIX A - EXAMPLESA-1.EXAMPLE 1(Dual Trip Point )Require an alarm to be activated when the pressure exceeds 50 PSI and a second alarm tobe activa
APPENDIX A - EXAMPLESA-2.EXAMPLE 2 (Trip Band )Require an alarm to be activated when the pressure falls out of an acceptance band of 25PSI to 50 PSI
APPENDIX A - EXAMPLESA-3.When the pressure is under 25 PSI, the display will prompt with “LOW” and the output alarmwill be active. The alarm will b
APPENDIX B - INSTALLATIONB-1.INSTALLATIONThe Relay Option Board(KKY8924-1) is mounted to the CPU bd. assy.on standoffs as shown.(10) m/f _” standoff
.10/24/01DLR334 SERIESADDENDUM 1TWO RELAYS AND SETPOINTS OPTIONOPERATION/INSTALLATION MANUALTABLE OF CONTENTSSECTION DESCRIPTION PAGE1 GENERAL INTROD
1.ADDENDUM 1 TWO RELAYS AND SETPOINTS OPTION FOR DLR3341. GENERAL INTRODUCTIONThe Analog / Relay / RPM Option board (KKY8924-) can be obtained as a Re
2.♦ Trip point settability: Set in display (engineering) units with resolution ofthe base unit configuration. In “run” mode set inbase.♦ Trip point
3.OUT 2 COM OUT 2 COM TB3-65. LOGIC OUTPUT:The logic output is available on the 1/0 terminal block TB2 on the CPU assembly.Trip 1: TB2-2Trip 2: TB2-3
4.keys.• After entering the desired value press the “ENTER” key to accept this value. Step to the next set up using the down ⇓ key.TRIP PT MENU TABLE
5.HYST2.H ±XXXXX0Hysteresis upper trip point 2 value.HYST2.L DESCENDASCENDHysteresis lower trip point 2 applies to descending data.Hysteresis lower tr
6."DISPLAY" parameter to "MODIFY" in the "TRIP PT” Menu".TRIP POINT VALUE RECALL: Recall the Trip Point values by pressi
7.9. SERIAL I/OAll Trip point menu parameters can be recalled or entered via the Serial Full Duplex whenin the setup mode. For full details of the tr