Condec DLR334 Series User Manual

Browse online or download User Manual for Equipment Condec DLR334 Series. Condec DLR334 Series User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 13
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
.
DLR334 Series
TWO RELAYS AND
SETPOINTS OPTION
OPERATION/INSTALLATION
MANUAL
PN 74844
Page view 0
1 2 3 4 5 6 ... 12 13

Summary of Contents

Page 1 - SETPOINTS OPTION

.DLR334 SeriesTWO RELAYS ANDSETPOINTS OPTIONOPERATION/INSTALLATIONMANUAL PN 74844

Page 2 - TABLE OF CONTENTS

APPENDIX A - EXAMPLESA-1.EXAMPLE 1(Dual Trip Point )Require an alarm to be activated when the pressure exceeds 50 PSI and a second alarm tobe activa

Page 3 - ADDENDUM 1

APPENDIX A - EXAMPLESA-2.EXAMPLE 2 (Trip Band )Require an alarm to be activated when the pressure falls out of an acceptance band of 25PSI to 50 PSI

Page 4 - 4. RELAY WIRING:

APPENDIX A - EXAMPLESA-3.When the pressure is under 25 PSI, the display will prompt with “LOW” and the output alarmwill be active. The alarm will b

Page 5 - 5. LOGIC OUTPUT:

APPENDIX B - INSTALLATIONB-1.INSTALLATIONThe Relay Option Board(KKY8924-1) is mounted to the CPU bd. assy.on standoffs as shown.(10) m/f _” standoff

Page 6

.10/24/01DLR334 SERIESADDENDUM 1TWO RELAYS AND SETPOINTS OPTIONOPERATION/INSTALLATION MANUALTABLE OF CONTENTSSECTION DESCRIPTION PAGE1 GENERAL INTROD

Page 7

1.ADDENDUM 1 TWO RELAYS AND SETPOINTS OPTION FOR DLR3341. GENERAL INTRODUCTIONThe Analog / Relay / RPM Option board (KKY8924-) can be obtained as a Re

Page 8

2.♦ Trip point settability: Set in display (engineering) units with resolution ofthe base unit configuration. In “run” mode set inbase.♦ Trip point

Page 9 - 9. SERIAL I/O

3.OUT 2 COM OUT 2 COM TB3-65. LOGIC OUTPUT:The logic output is available on the 1/0 terminal block TB2 on the CPU assembly.Trip 1: TB2-2Trip 2: TB2-3

Page 10

4.keys.• After entering the desired value press the “ENTER” key to accept this value. Step to the next set up using the down ⇓ key.TRIP PT MENU TABLE

Page 11

5.HYST2.H ±XXXXX0Hysteresis upper trip point 2 value.HYST2.L DESCENDASCENDHysteresis lower trip point 2 applies to descending data.Hysteresis lower tr

Page 12 - APPENDIX A - EXAMPLES

6."DISPLAY" parameter to "MODIFY" in the "TRIP PT” Menu".TRIP POINT VALUE RECALL: Recall the Trip Point values by pressi

Page 13

7.9. SERIAL I/OAll Trip point menu parameters can be recalled or entered via the Serial Full Duplex whenin the setup mode. For full details of the tr